Specification of GP4107G1D
GP-4107G
Model: GP4107G1D(PFXGP4107G1D)
Monochrome LCD (16 Shades) / Display Resolution: 200x80 pixels
Functional Specification
Display Type |
STN Monochrome LCD |
Display Size |
3.4" |
Resolution |
200 x 80 pixels |
Dot pitch |
W0.4 x H0.4 mm [W0.02 x H0.02 in.] |
Effective Display Area |
79.985 x 31.985 mm |
Display Colors |
Monochrome Green/Red/Orange (16 Levels) |
Backlight |
Green/Red LED (User nonreplaceable parts. Factory replacement required.)*1 |
Brightness Control |
16 Levels (Adjusted with the touch panel) |
Contrast Control |
8 Levels (Adjusted with the touch panel) |
Backlight Service Life |
Green: 50,000 hrs. or more, Red 10,000 hrs. or more (each in continuous operation at 25℃ before backlight brightness decreases to 50%) |
Language Fonts |
Japanese, ASCII, Chinese (Simplified), Chinese (Traditional), Korean, Cyrillic, Thai*2 |
Character Sizes |
Standard font: 8 x 8, 8 x 16, 16 x 16 and 32 x 32 pixel fonts, Stroke font: 6 to 80 pixel fonts, Image font: 8 to 72 pixel fonts |
Font Sizes |
Standard font: Width can be expanded up to 8 times. Height can be expanded up to 8 times.*3 |
Text |
8 x 16 dots |
25 char. x 5 rows |
16 x 16 dots |
12 char. x 5 rows |
32 x 32 dots |
6 char. x 2 rows |
Application Memory |
FLASH EPROM 2.2 MB*4 |
Data Backup |
128KB*5 |
Clock Accuracy |
Uses the clock of an external device*6 |
Touch Panel Type |
Resistive Film (analog) |
Touch Panel Resolution |
1,024 x 1,024 |
Touch Panel Service Life |
1,000,000 times or more |
Interface |
Ethernet (LAN) |
IEEE802.3i/IEEE802.3u, 10BASE-T/100BASE-TX, Connector: Modular jack (RJ-45) x 1 |
USB (TYPE-A) |
Conforms to USB2.0 (Type-A) x 1, Power Supply Voltage: DC 5 V ±5 %, Communication Distance: 5 m or less*7 |
USB (mini-B) |
Conforms to USB2.0 (mini-B) x 1, Communication Distance: 5 m or less |
-
*1 The backlight burnout detection function is not supported.
-
*2 Please refer to the GP-Pro EX reference manual for details on font types and character codes.
-
*3 Other font sizes can be set up with the Editor software.
-
*4 Capacity available for user application.
-
*5 Application memory can provide 128KB for Data Backup. For further information, please refer to the GP-Pro EX reference manual.
-
*6 Set up the “Clock Updates“ feature with the Editor software. Please refer to the GP-Pro EX reference manual “Common” - “Clock Update Settings” for details.
-
*7 If connecting a bar code reader to the GP, be sure to supply power from an external source (such as a self-powered hub). If connecting a bar code reader to the GP, be sure to supply power from an external source (such as a self-powered hub). If you supply
General Specification
International Safety Standards |
|
Rated Input Voltage |
DC 24 V |
Input Voltage Limits |
DC 19.2 to 28.8 V |
Allowable Voltage Drop |
3 ms or less |
Power Consumption |
6 W or less |
In-Rush Current |
30 A or less |
Voltage Endurance |
AC 1,000 V, 20 mA for 1 min (between charging and FG terminals) |
Insulation Resistance |
DC 500 V, 10 MΩ or more (between charging and FG terminals) |
Surrounding Air Temperature |
0 to 50 ℃*8 |
Storage Temperature |
-20 to +60 ℃ |
Ambient Humidity |
10 to 90 % RH (Wet bulb temperature: 39 ℃ or less - no condensation.) |
Storage Humidity |
10 to 90 % RH (Wet bulb temperature: 39 ℃ or less - no condensation.) |
Dust |
0.1 mg/m³ or less (non-conductive levels) |
Pollution Degree |
For use in Pollution Degree 2 environment |
Atmosphere |
Free of corrosive gases |
Air Pressure (altitude range) |
800 to 1,114 hPa (2,000 m above sea level or less) |
Vibration Resistance |
IEC/EN61131-2 compliant, 5 to 9 Hz Single amplitude 3.5 mm [0.14 in.], 9 to 150 Hz Fixed acceleration: 9.8 m/s², X, Y, Z directions for 10 cycles (100 min) |
Concussion Resistance |
IEC/EN61131-2 compliant, 147 m/s², X, Y, Z directions for 3 times |
Noise Immunity |
Noise Voltage: 1,000 Vp-p, Pulse Duration: 1 µs, Rise Time: 1 ns, (via noise simulator) |
Noise Immunity (Fast Transient Burst Noise) |
Power Line: 2 kV (IEC/EN61000-4-4) |
Electrostatic Discharge Immunity |
Contact Discharge Method: 6 kV/Air Discharge Method: 8 kV (IEC/EN61000-4-2 Level 3) |
Grounding |
Functional grounding: Grounding resistance of 100Ω, 2mm² or thicker wire, or your country's applicable standard. (Same for FG and SG terminals) |
Structure |
IP65f NEMA #250 TYPE 4X/13 (on the front panel when properly installed in an enclosure)*9 |
Installation Configuration |
Embedded panel |
Cooling Method |
Natural air circulation |
Weight Approx. |
0.2 kg [0.4 lb] or less (display unit only) |
External Dimensions |
W116.5 x H77.5 x D28 mm [W4.59 x H3.05 x D1.1 in.] |
Panel Cut Dimensions |
W105 x H66 mm [W4.13 x H2.6 in.], Panel thickness area: 1 to 5 mm [0.04 to 0.2 in.]*10 |
-
*8 When using in an environment where the temperature becomes or exceeds 40 ℃ for an extended period of time, the screen contrast level may decrease from its original level of brightness.
-
*9 The front face of the GP unit, installed in a solid panel, has been tested using, conditions equivalent to the standards shown in the specification. Even though the, GP unit's level of resistance is equivalent to these standards, oils that should have, no
-
*10 Regarding dimensional tolerance, everything +1/-0 mm [+0.04/-0 in.] and R in angle are below R3 [R0.12 in.]. Even if panel thickness is within recommend range for “Panel Cut Dimensions”, the panel could warp, depending on panel’s material, size, and insta
External Dimensions / Interfaces / Panel Cut-out
-
*11 A protective dropping hook is included with GP units rev.1 or higher.
|
|
|
|
Product and Technology News
Pressure and Temperature Transmitter
Download Catalogue
|