Specification of GP4107G1D

GP-4107G
Model: GP4107G1D(PFXGP4107G1D)

Thumbnail
  • LED (Green/Orange/Red)
  • USB

 

  •  


  •  
Monochrome LCD   (16 Shades) /   Display Resolution: 200x80 pixels 

Functional Specification

Display Type STN Monochrome LCD
Display Size 3.4"
Resolution 200 x 80 pixels
Dot pitch W0.4 x H0.4 mm [W0.02 x H0.02 in.]
Effective Display Area 79.985 x 31.985 mm
Display Colors Monochrome Green/Red/Orange (16 Levels)
Backlight Green/Red LED (User nonreplaceable parts. Factory replacement required.)*1
Brightness Control 16 Levels (Adjusted with the touch panel)
Contrast Control 8 Levels (Adjusted with the touch panel)
Backlight Service Life Green: 50,000 hrs. or more, Red 10,000 hrs. or more (each in continuous operation at 25℃ before backlight brightness decreases to 50%)
Language Fonts Japanese, ASCII, Chinese (Simplified), Chinese (Traditional), Korean, Cyrillic, Thai*2
Character Sizes Standard font: 8 x 8, 8 x 16, 16 x 16 and 32 x 32 pixel fonts, Stroke font: 6 to 80 pixel fonts, Image font: 8 to 72 pixel fonts
Font Sizes Standard font: Width can be expanded up to 8 times. Height can be expanded up to 8 times.*3
Text 8 x 16 dots 25 char. x 5 rows
16 x 16 dots 12 char. x 5 rows
32 x 32 dots 6 char. x 2 rows
Application Memory FLASH EPROM 2.2 MB*4
Data Backup 128KB*5
Clock Accuracy Uses the clock of an external device*6
Touch Panel Type Resistive Film (analog)
Touch Panel Resolution 1,024 x 1,024
Touch Panel Service Life 1,000,000 times or more
Interface Ethernet (LAN) IEEE802.3i/IEEE802.3u, 10BASE-T/100BASE-TX, Connector: Modular jack (RJ-45) x 1
USB (TYPE-A) Conforms to USB2.0 (Type-A) x 1, Power Supply Voltage: DC 5 V ±5 %, Communication Distance: 5 m or less*7
USB (mini-B) Conforms to USB2.0 (mini-B) x 1, Communication Distance: 5 m or less
  1. *1     The backlight burnout detection function is not supported.
  2. *2     Please refer to the GP-Pro EX reference manual for details on font types and character codes.
  3. *3     Other font sizes can be set up with the Editor software.
  4. *4     Capacity available for user application.
  5. *5     Application memory can provide 128KB for Data Backup. For further information, please refer to the GP-Pro EX reference manual.
  6. *6     Set up the “Clock Updates“ feature with the Editor software. Please refer to the GP-Pro EX reference manual “Common” - “Clock Update Settings” for details.
  7. *7     If connecting a bar code reader to the GP, be sure to supply power from an external source (such as a self-powered hub). If connecting a bar code reader to the GP, be sure to supply power from an external source (such as a self-powered hub). If you supply

General Specification

International Safety Standards
  • UL,cUL(508) Listed
     
  •  
  • ANSI/CSA(UL508+1604) Listed
     
  •  
  • CE
     
  •  
  • C-Tick
     
  •  
  • KC
     
  •  
  • Gost-R
     
Rated Input Voltage DC 24 V
Input Voltage Limits DC 19.2 to 28.8 V
Allowable Voltage Drop 3 ms or less
Power Consumption 6 W or less
In-Rush Current 30 A or less
Voltage Endurance AC 1,000 V, 20 mA for 1 min (between charging and FG terminals)
Insulation Resistance DC 500 V, 10 MΩ or more (between charging and FG terminals)
Surrounding Air Temperature 0 to 50 ℃*8
Storage Temperature -20 to +60 ℃
Ambient Humidity 10 to 90 % RH (Wet bulb temperature: 39 ℃ or less - no condensation.)
Storage Humidity 10 to 90 % RH (Wet bulb temperature: 39 ℃ or less - no condensation.)
Dust 0.1 mg/m³ or less (non-conductive levels)
Pollution Degree For use in Pollution Degree 2 environment
Atmosphere Free of corrosive gases
Air Pressure (altitude range) 800 to 1,114 hPa (2,000 m above sea level or less)
Vibration Resistance IEC/EN61131-2 compliant, 5 to 9 Hz Single amplitude 3.5 mm [0.14 in.], 9 to 150 Hz Fixed acceleration: 9.8 m/s², X, Y, Z directions for 10 cycles (100 min)
Concussion Resistance IEC/EN61131-2 compliant, 147 m/s², X, Y, Z directions for 3 times
Noise Immunity Noise Voltage: 1,000 Vp-p, Pulse Duration: 1 µs, Rise Time: 1 ns, (via noise simulator)
Noise Immunity (Fast Transient Burst Noise) Power Line: 2 kV (IEC/EN61000-4-4)
Electrostatic Discharge Immunity Contact Discharge Method: 6 kV/Air Discharge Method: 8 kV (IEC/EN61000-4-2 Level 3)
Grounding Functional grounding: Grounding resistance of 100Ω, 2mm² or thicker wire, or your country's applicable standard. (Same for FG and SG terminals)
Structure IP65f NEMA #250 TYPE 4X/13 (on the front panel when properly installed in an enclosure)*9
Installation Configuration Embedded panel
Cooling Method Natural air circulation
Weight Approx. 0.2 kg [0.4 lb] or less (display unit only)
External Dimensions W116.5 x H77.5 x D28 mm [W4.59 x H3.05 x D1.1 in.]
Panel Cut Dimensions W105 x H66 mm [W4.13 x H2.6 in.], Panel thickness area: 1 to 5 mm [0.04 to 0.2 in.]*10
  1. *8     When using in an environment where the temperature becomes or exceeds 40 ℃ for an extended period of time, the screen contrast level may decrease from its original level of brightness.
  2. *9     The front face of the GP unit, installed in a solid panel, has been tested using, conditions equivalent to the standards shown in the specification. Even though the, GP unit's level of resistance is equivalent to these standards, oils that should have, no
  3. *10   Regarding dimensional tolerance, everything +1/-0 mm [+0.04/-0 in.] and R in angle are below R3 [R0.12 in.]. Even if panel thickness is within recommend range for “Panel Cut Dimensions”, the panel could warp, depending on panel’s material, size, and insta